Glass Insulated/Glass Braided Tinned Copper, Silicone, Glass Braided Silicon, Glass Insulated/Glass Braided Nickel

| APPLICATION | For use in heating and refrigeration equipment and where ambient temperatures exceed 90°C, and mechanical strength is required. |
|---|---|
| CONSTRUCTION - CONDUCTOR | Tinned annealed copper wire. |
| INSULATION | Varnish impregnated Glass Braid. |
| COLOURS | Natural, red, black, white, blue & green NOTE: Not all size and colours available ex-stock, minimum order quantities may apply. |
| TEMPERATURE | 0°C to +150°C |
| VOLTAGE | 0.6/1kV |
| STANDARDS | AS 3158, AS1125 |
| BAMBACH NUMBER | NOMINAL AREA mm | STRANDING No. of Strands/mm |
NOMINAL DIAMETER mm | BENDING RADIUS mm | CURRENT RATING Amps | WEIGHT Kg/m |
|---|---|---|---|---|---|---|
| 16100 | 0.75 | 24/0.20 | 3.2 | 25.6 | 20 | 0.014 |
| 17880 | 1 | 32/0.20 | 3.4 | 27.2 | 24 | 0.021 |
| 19520 | 1.5 | 30/0.25 | 3.6 | 28.8 | 31 | 0.041 |
| 21000 | 2.5 | 50/0.25 | 4.1 | 32.8 | 43 | 0.06 |
| 22280 | 4 | 56/0.30 | 4.8 | 38.4 | 58 | 0.073 |